Wiring Lab runs 89 checks on the project, each with a stable code and a reference to the standard behind it. Choose the country of the site: you get the electrical profile the software proposes and the full list of checks you will see in the Validation window.
| NEC profile | CEI 64-8 / IEC 60364 profile | No calculation profile | |
|---|---|---|---|
| Typical supply | 120 V · 60 Hz | 230 V · 50 Hz | to be set |
| Typical outlet protection | 20 A | 16 A | to be set |
| Ampacity table | AWG, NEC table | mm², IEC table | not available |
| Minimum conductor size required for the outlet | none: ampacity decides | 1.5 mm² up to 10 A, then 2.5 mm² | not available |
| Accepted voltage drop | 3% on the branch circuit, 5% overall | 4% — CEI 64-8 §525 | cites both, judges neither |
| Checks that apply only there | 1 — loudspeaker/signal separation in conduit (AVIXA) | 1 in Italy — minimum conduit diameter | none |
| Code | Check | Standard cited | Severity |
|---|---|---|---|
| Safety | |||
N001_ELEC_SITE_DATA_MISSING | Project electrical data missing | NEC / IEC-60364 | Error |
N004_ELEC_CODE_COUNTRY_MISMATCH | Standard reference differs from the country's | WL-INTEGRITY | Warning |
N014_RACK_FEED_UNDERSIZED | Rack supply cable undersized for the rack load | NEC | Warning |
V021_CONDUIT_POWER_SIGNAL_MIX | Different classes in the same conduit (power / signal / loudspeaker) | EN-50174-2 | Error |
V030_NO_GROUNDING_TOPOLOGY | Grounding topology not defined | TIA-607-D | Note |
V031_AC_MAINS_INCONSISTENT | Inconsistent AC mains across the project | IEC-60364 | Warning |
V033_RACK_MIXED_VOLTAGE | Mixed AC voltages in the rack | IEC-60364 | Error |
V072_RACK_THERMAL_LOAD | High rack heat load | WL-CONVENTIONS | Warning |
V090_GROUNDING_NODE_ISOLATED | Isolated grounding node | TIA-607-D | Warning |
V091_GROUNDING_BOND_NO_AWG | Grounding bond with no AWG | TIA-607-D | Note |
V092_GROUNDING_DISCONNECTED_GRAPH | Grounding topology split into islands | TIA-607-D | Error |
V093_GROUNDING_NO_BUILDING_REFERENCE | Missing reference to the building safety ground | TIA-607-D | Warning |
V100_PDU_OVERLOAD | PDU/UPS overloaded (beyond the fuse) | IEC-60364 | Error |
V102_BONDING_UNDERSIZED | Bonding conductor undersized for its length | TIA-607-D | Warning |
| Infrastructure | |||
N005_CV25_AMP_NOT_DECLARED | 25 V line on an amplifier declared 70/100 V only | WL-CONVENTIONS | Warning |
N006_CV_LINE_DATA_MISSING | Constant-voltage line: data missing | WL-INTEGRITY | Note |
N013_CONDUIT_JAM_RISK | Three cables at risk of jamming in the conduit | NEC | Note |
N015_IT_TUBE_DIAMETER | Conduit below the minimum diameter (Italy) | CEI 64-8 | Note |
N016_SPEAKER_SIGNAL_SEPARATION_AVIXA | Loudspeaker lines and other signals in the same conduit (AVIXA, US projects) | AVIXA-F502 | Warning |
V010_CABLE_NO_LABEL | Cable with no label | TIA-606-C | Warning |
V011_CABLE_NO_LENGTH_FINAL | Cable with no length (late design stage) | AVIXA-F501 | Warning |
V012_CONNECTOR_NO_MODEL | Connector with no commercial model | AVIXA-F501 | Warning |
V013_DUPLICATE_LABELS | Duplicate cable labels | TIA-606-C | Warning |
V014_LABEL_FORMAT_F501 | Label does not conform to AVIXA F501 | AVIXA-F501 | Note |
V018_CABLE_OPEN_ENDED | Cable connected at one end only | WL-INTEGRITY | Error |
V020_CONDUIT_FILL_OVER | Conduit fill ratio over the limit | EN-50174-2 | Warning |
V022_CONDUIT_NO_MATERIAL | Conduit with no material | TIA-569-D | Note |
V029_CONDUIT_DUPLICATE_NAME | Duplicate conduit names | TIA-606-C | Warning |
V032_POWER_PLUG_MIX | Mixed AC outlet types in the rack | WL-CONVENTIONS | Note |
V034_RACK_OVER_SINGLE_LINE_CAPACITY | Rack possibly beyond the capacity of a single AC circuit | IEC-60364 | Warning |
V035_RACK_NO_PDU_DECLARED | Rack with powered equipment but no declared PDU | WL-CONVENTIONS | Note |
V036_PDU_RATED_BELOW_LOAD | PDU undersized for the rack load | IEC-60364 | Warning |
V037_PDU_OUTLET_INSUFFICIENT | PDU with too few outlets for the rack equipment | WL-CONVENTIONS | Note |
V063_ELEMENT_NO_SIGLA | Item with no designation | TIA-606-C | Warning |
V064_DEVICE_NOT_CABLED | Item not cabled | AVIXA-F501 | Warning |
V080_NETWORK_NO_VLAN | AoIP/network with no VLAN or subnet | WL-CONVENTIONS | Note |
V081_SUBNET_OVERLAP | Subnets with overlapping IP/CIDR ranges | WL-INTEGRITY | Error |
V082_AOIP_VLAN_MIX | AoIP and management/control on the same VLAN | WL-CONVENTIONS | Warning |
V101_PDU_NEAR_LIMIT | PDU/UPS close to the limit (>80% of the fuse) | IEC-60364 | Warning |
V121_LEVEL_MISMATCH | +4 dBu ↔ −10 dBV line connection with no matching (advice) | WL-CONVENTIONS | Note |
V130_CONDUIT_BEND_RADIUS | Cable bend radius incompatible with the conduit bends | TIA-569-D | Warning |
V132_TR_PER_FLOOR | Backbone terminating floor with no rack/TR (multi-building) | TIA-569-D | Note |
V133_FIBER_COLORS_INCONSISTENT | Fibre backbone with no fibre count (TIA-598 colour scheme) | TIA-598-D | Note |
V140_SMPTE2110_NETWORK | SMPTE ST 2110: a dedicated media network and per-flow bandwidth are required | SMPTE-2110 | Warning |
V141_NDI_BANDWIDTH | Estimated NDI bandwidth against the network link | WL-CONVENTIONS | Note |
V142_HDBASET_LIMITS | HDBaseT: 100 m maximum length and minimum category | HDBaseT | Warning |
V150_IGMP_QUERIER | IGMP querier for the multicast AoIP VLAN | IETF-IGMP | Error |
V151_STATIC_IP_IN_DHCP_POOL | Static IP inside the DHCP pool | WL-INTEGRITY | Warning |
V163_SPECS_MISSING | Specifications missing for the checks | WL-INTEGRITY | Note |
V164_VIDEO_IO_OVERSUB | Video I/O over-subscribed | WL-INTEGRITY | Warning |
V165_SPEAKER_NETWORK_IMPEDANCE | Loudspeaker network impedance against the amplifier | WL-CONVENTIONS | Warning |
V166_SPEAKER_AMP_MATCH | Amplifier to loudspeaker matching | WL-CONVENTIONS | Note |
V170_CABLE_CONNECTOR_MISMATCH | Commercial cable incompatible with the connectors on the run | WL-INTEGRITY | Warning |
V171_JUNCTION_CABLE_SECTION | Cable size outside the range of the splice | WL-INTEGRITY | Warning |
V172_CV_LINE_DROP | 70/100 V line loss beyond the target | WL-CONVENTIONS | Warning |
| Cabling | |||
V017_CABLE_LENGTH_OVER_MAX | Cable beyond the maximum length for its signal | WL-CONVENTIONS | Warning |
| Model consistency | |||
N007_MC_CIRCUITS_OVER_PAIRS | Multicore: more circuits than the cable has pairs | WL-INTEGRITY | Warning |
N008_MC_CHANNEL_OVER_PAIRS | Multicore: channel beyond the cable's pairs | WL-INTEGRITY | Warning |
N009_MC_SPARE_CHANNELS | Multicore: spare channels | WL-INTEGRITY | Note |
N010_CABLE_END_PORT_MISSING | Cable with one end on a port that does not exist | WL-INTEGRITY | Warning |
N011_CABLE_END_MISSING | Cable missing an end | WL-INTEGRITY | Warning |
N012_SECTION_UNIT_CORRECTED | Conductor size written in mm instead of mm² | WL-INTEGRITY | Note |
V016_LABEL_NUMBERING_GAP | Gap in the label numbering | TIA-606-C | Note |
V023_CONDUIT_EMPTY | Conduit with no cables assigned | WL-INTEGRITY | Note |
V024_CONDUIT_NO_ROOMS | Conduit with no documented rooms | EN-50174-2 | Note |
V025_CONDUIT_FILL_OVER_RECOMMENDED | Conduit beyond the recommended fill ratio (40%) | EN-50174-2 | Note |
V026_CABLE_CROSS_ROOM_NO_CONDUIT | Cross-room cable with no conduit assigned | EN-50174-2 | Note |
V027_CONDUIT_ENDPOINT_INVALID | Conduit whose ends are not on valid points | EN-50174-2 | Warning |
V028_CABLE_ORPHAN_CONDUIT_SEGMENT | Cable with a segment on a deleted conduit | EN-50174-2 | Warning |
V060_ORPHAN_CONNECTIONS | Connection with a missing endpoint | WL-INTEGRITY | Error |
V061_DUPLICATE_RACK_SIGLE | Duplicate rack/wall-plate designations | TIA-606-C | Error |
V062_ROOM_TYPO_VARIANTS | Spelling variants of the same room | TIA-606-C | Warning |
V071_RACK_UNIT_COLLISION | Collision between units in the same rack | WL-INTEGRITY | Error |
V174_CONTAINER_NO_ROOM | Position or point with no room | WL-INTEGRITY | Note |
| Racks and layout | |||
V040_CONTAINER_NO_ROOM | Container with no position | TIA-606-C | Note |
V041_WALL_PANEL_NO_PORTS | Wall panel with no I/O | WL-INTEGRITY | Note |
V070_RACK_U_OVERFLOW | Rack U usage beyond capacity | WL-INTEGRITY | Error |
V110_RACK_HEAVY_HIGH | Heavy equipment mounted high (advice) | WL-CONVENTIONS | Note |
V111_RACK_VENTILATION_ADVISORY | Heat load with no declared ventilation (advice) | WL-CONVENTIONS | Note |
V112_RACK_LACING_ADVISORY | Densely filled rack with no lacing bar (advice) | WL-CONVENTIONS | Note |
V113_RACK_CLEARANCE_BLOCKED | Ventilation clearance obstructed (advice) | WL-CONVENTIONS | Note |
V131_RACK_DEPTH_EXCEEDED | Equipment deeper than the rack | TIA-569-D | Warning |
V160_CONTAINER_NO_PRODUCT | Rack or wall panel with no product assigned | WL-INTEGRITY | Warning |
| Bill of materials | |||
V050_CABLE_NO_COMMERCIAL | Cable with no commercial model (BOM) | WL-INTEGRITY | Note |
V135_SPARES_DISABLED | Spares switched off — check warning | WL-CONVENTIONS | Note |
| Project documents | |||
N002_PROJECT_COUNTRY_MISSING | Project country missing | WL-INTEGRITY | Error |
V001_PROJECT_COVER_INCOMPLETE | Incomplete cover sheet | AVIXA-D401 | Warning |
V002_PROJECT_REVISION_MISSING | Late design stage with no revision | AVIXA-D401 | Warning |
V134_REVISION_STAGE_MISMATCH | Title-block revision inconsistent with the design stage (advice) | WL-CONVENTIONS | Note |
The standard cited. Where a standard is named, the check comes from it and the message quotes it in full, with the clause. The entries WL-CONVENTIONS and WL-INTEGRITY are not standards: they are the model-consistency checks — a cable missing an end, two identical designations, a conductor size written in mm instead of mm². We run them because no standard covers them, and because an inconsistent design cannot even be checked.
Why the electrical standard changes and the others do not. The cabling and documentation standards Wiring Lab cites — TIA-606, TIA-607, TIA-569, EN 50174-2, the AVIXA ones — are international or regional, and the check is identical everywhere. Electrical installation standards, on the other hand, are national: there the reference changes, and with two profiles (NEC and CEI 64-8 / IEC 60364) so do the thresholds.
Two checks apply in one country only: the minimum conduit diameter (Italy) and the separation between loudspeaker lines and other signals in the same conduit (United States, required by AVIXA). They appear in the list only when you choose that country.
Wiring Lab helps you check a design against the requirements of the standards it cites, and reports the reference behind every check. It is not a certification body and it does not replace verification by a qualified professional.