Checks

Every check Wiring Lab runs, and the standard behind it

Wiring Lab runs 89 checks on the project, each with a stable code and a reference to the standard behind it. Choose the country of the site: you get the electrical profile the software proposes and the full list of checks you will see in the Validation window.

What changes with the country
NEC profile CEI 64-8 / IEC 60364 profile No calculation profile
Typical supply120 V · 60 Hz230 V · 50 Hzto be set
Typical outlet protection20 A16 Ato be set
Ampacity tableAWG, NEC tablemm², IEC tablenot available
Minimum conductor size required for the outletnone: ampacity decides1.5 mm² up to 10 A, then 2.5 mm²not available
Accepted voltage drop3% on the branch circuit, 5% overall4% — CEI 64-8 §525cites both, judges neither
Checks that apply only there1 — loudspeaker/signal separation in conduit (AVIXA)1 in Italy — minimum conduit diameternone
Code Check Standard cited Severity
Safety
N001_ELEC_SITE_DATA_MISSINGProject electrical data missingNEC / IEC-60364Error
N004_ELEC_CODE_COUNTRY_MISMATCHStandard reference differs from the country'sWL-INTEGRITYWarning
N014_RACK_FEED_UNDERSIZEDRack supply cable undersized for the rack loadNECWarning
V021_CONDUIT_POWER_SIGNAL_MIXDifferent classes in the same conduit (power / signal / loudspeaker)EN-50174-2Error
V030_NO_GROUNDING_TOPOLOGYGrounding topology not definedTIA-607-DNote
V031_AC_MAINS_INCONSISTENTInconsistent AC mains across the projectIEC-60364Warning
V033_RACK_MIXED_VOLTAGEMixed AC voltages in the rackIEC-60364Error
V072_RACK_THERMAL_LOADHigh rack heat loadWL-CONVENTIONSWarning
V090_GROUNDING_NODE_ISOLATEDIsolated grounding nodeTIA-607-DWarning
V091_GROUNDING_BOND_NO_AWGGrounding bond with no AWGTIA-607-DNote
V092_GROUNDING_DISCONNECTED_GRAPHGrounding topology split into islandsTIA-607-DError
V093_GROUNDING_NO_BUILDING_REFERENCEMissing reference to the building safety groundTIA-607-DWarning
V100_PDU_OVERLOADPDU/UPS overloaded (beyond the fuse)IEC-60364Error
V102_BONDING_UNDERSIZEDBonding conductor undersized for its lengthTIA-607-DWarning
Infrastructure
N005_CV25_AMP_NOT_DECLARED25 V line on an amplifier declared 70/100 V onlyWL-CONVENTIONSWarning
N006_CV_LINE_DATA_MISSINGConstant-voltage line: data missingWL-INTEGRITYNote
N013_CONDUIT_JAM_RISKThree cables at risk of jamming in the conduitNECNote
N015_IT_TUBE_DIAMETERConduit below the minimum diameter (Italy)CEI 64-8Note
N016_SPEAKER_SIGNAL_SEPARATION_AVIXALoudspeaker lines and other signals in the same conduit (AVIXA, US projects)AVIXA-F502Warning
V010_CABLE_NO_LABELCable with no labelTIA-606-CWarning
V011_CABLE_NO_LENGTH_FINALCable with no length (late design stage)AVIXA-F501Warning
V012_CONNECTOR_NO_MODELConnector with no commercial modelAVIXA-F501Warning
V013_DUPLICATE_LABELSDuplicate cable labelsTIA-606-CWarning
V014_LABEL_FORMAT_F501Label does not conform to AVIXA F501AVIXA-F501Note
V018_CABLE_OPEN_ENDEDCable connected at one end onlyWL-INTEGRITYError
V020_CONDUIT_FILL_OVERConduit fill ratio over the limitEN-50174-2Warning
V022_CONDUIT_NO_MATERIALConduit with no materialTIA-569-DNote
V029_CONDUIT_DUPLICATE_NAMEDuplicate conduit namesTIA-606-CWarning
V032_POWER_PLUG_MIXMixed AC outlet types in the rackWL-CONVENTIONSNote
V034_RACK_OVER_SINGLE_LINE_CAPACITYRack possibly beyond the capacity of a single AC circuitIEC-60364Warning
V035_RACK_NO_PDU_DECLAREDRack with powered equipment but no declared PDUWL-CONVENTIONSNote
V036_PDU_RATED_BELOW_LOADPDU undersized for the rack loadIEC-60364Warning
V037_PDU_OUTLET_INSUFFICIENTPDU with too few outlets for the rack equipmentWL-CONVENTIONSNote
V063_ELEMENT_NO_SIGLAItem with no designationTIA-606-CWarning
V064_DEVICE_NOT_CABLEDItem not cabledAVIXA-F501Warning
V080_NETWORK_NO_VLANAoIP/network with no VLAN or subnetWL-CONVENTIONSNote
V081_SUBNET_OVERLAPSubnets with overlapping IP/CIDR rangesWL-INTEGRITYError
V082_AOIP_VLAN_MIXAoIP and management/control on the same VLANWL-CONVENTIONSWarning
V101_PDU_NEAR_LIMITPDU/UPS close to the limit (>80% of the fuse)IEC-60364Warning
V121_LEVEL_MISMATCH+4 dBu ↔ −10 dBV line connection with no matching (advice)WL-CONVENTIONSNote
V130_CONDUIT_BEND_RADIUSCable bend radius incompatible with the conduit bendsTIA-569-DWarning
V132_TR_PER_FLOORBackbone terminating floor with no rack/TR (multi-building)TIA-569-DNote
V133_FIBER_COLORS_INCONSISTENTFibre backbone with no fibre count (TIA-598 colour scheme)TIA-598-DNote
V140_SMPTE2110_NETWORKSMPTE ST 2110: a dedicated media network and per-flow bandwidth are requiredSMPTE-2110Warning
V141_NDI_BANDWIDTHEstimated NDI bandwidth against the network linkWL-CONVENTIONSNote
V142_HDBASET_LIMITSHDBaseT: 100 m maximum length and minimum categoryHDBaseTWarning
V150_IGMP_QUERIERIGMP querier for the multicast AoIP VLANIETF-IGMPError
V151_STATIC_IP_IN_DHCP_POOLStatic IP inside the DHCP poolWL-INTEGRITYWarning
V163_SPECS_MISSINGSpecifications missing for the checksWL-INTEGRITYNote
V164_VIDEO_IO_OVERSUBVideo I/O over-subscribedWL-INTEGRITYWarning
V165_SPEAKER_NETWORK_IMPEDANCELoudspeaker network impedance against the amplifierWL-CONVENTIONSWarning
V166_SPEAKER_AMP_MATCHAmplifier to loudspeaker matchingWL-CONVENTIONSNote
V170_CABLE_CONNECTOR_MISMATCHCommercial cable incompatible with the connectors on the runWL-INTEGRITYWarning
V171_JUNCTION_CABLE_SECTIONCable size outside the range of the spliceWL-INTEGRITYWarning
V172_CV_LINE_DROP70/100 V line loss beyond the targetWL-CONVENTIONSWarning
Cabling
V017_CABLE_LENGTH_OVER_MAXCable beyond the maximum length for its signalWL-CONVENTIONSWarning
Model consistency
N007_MC_CIRCUITS_OVER_PAIRSMulticore: more circuits than the cable has pairsWL-INTEGRITYWarning
N008_MC_CHANNEL_OVER_PAIRSMulticore: channel beyond the cable's pairsWL-INTEGRITYWarning
N009_MC_SPARE_CHANNELSMulticore: spare channelsWL-INTEGRITYNote
N010_CABLE_END_PORT_MISSINGCable with one end on a port that does not existWL-INTEGRITYWarning
N011_CABLE_END_MISSINGCable missing an endWL-INTEGRITYWarning
N012_SECTION_UNIT_CORRECTEDConductor size written in mm instead of mm²WL-INTEGRITYNote
V016_LABEL_NUMBERING_GAPGap in the label numberingTIA-606-CNote
V023_CONDUIT_EMPTYConduit with no cables assignedWL-INTEGRITYNote
V024_CONDUIT_NO_ROOMSConduit with no documented roomsEN-50174-2Note
V025_CONDUIT_FILL_OVER_RECOMMENDEDConduit beyond the recommended fill ratio (40%)EN-50174-2Note
V026_CABLE_CROSS_ROOM_NO_CONDUITCross-room cable with no conduit assignedEN-50174-2Note
V027_CONDUIT_ENDPOINT_INVALIDConduit whose ends are not on valid pointsEN-50174-2Warning
V028_CABLE_ORPHAN_CONDUIT_SEGMENTCable with a segment on a deleted conduitEN-50174-2Warning
V060_ORPHAN_CONNECTIONSConnection with a missing endpointWL-INTEGRITYError
V061_DUPLICATE_RACK_SIGLEDuplicate rack/wall-plate designationsTIA-606-CError
V062_ROOM_TYPO_VARIANTSSpelling variants of the same roomTIA-606-CWarning
V071_RACK_UNIT_COLLISIONCollision between units in the same rackWL-INTEGRITYError
V174_CONTAINER_NO_ROOMPosition or point with no roomWL-INTEGRITYNote
Racks and layout
V040_CONTAINER_NO_ROOMContainer with no positionTIA-606-CNote
V041_WALL_PANEL_NO_PORTSWall panel with no I/OWL-INTEGRITYNote
V070_RACK_U_OVERFLOWRack U usage beyond capacityWL-INTEGRITYError
V110_RACK_HEAVY_HIGHHeavy equipment mounted high (advice)WL-CONVENTIONSNote
V111_RACK_VENTILATION_ADVISORYHeat load with no declared ventilation (advice)WL-CONVENTIONSNote
V112_RACK_LACING_ADVISORYDensely filled rack with no lacing bar (advice)WL-CONVENTIONSNote
V113_RACK_CLEARANCE_BLOCKEDVentilation clearance obstructed (advice)WL-CONVENTIONSNote
V131_RACK_DEPTH_EXCEEDEDEquipment deeper than the rackTIA-569-DWarning
V160_CONTAINER_NO_PRODUCTRack or wall panel with no product assignedWL-INTEGRITYWarning
Bill of materials
V050_CABLE_NO_COMMERCIALCable with no commercial model (BOM)WL-INTEGRITYNote
V135_SPARES_DISABLEDSpares switched off — check warningWL-CONVENTIONSNote
Project documents
N002_PROJECT_COUNTRY_MISSINGProject country missingWL-INTEGRITYError
V001_PROJECT_COVER_INCOMPLETEIncomplete cover sheetAVIXA-D401Warning
V002_PROJECT_REVISION_MISSINGLate design stage with no revisionAVIXA-D401Warning
V134_REVISION_STAGE_MISMATCHTitle-block revision inconsistent with the design stage (advice)WL-CONVENTIONSNote
No check matches your search.

The standard cited. Where a standard is named, the check comes from it and the message quotes it in full, with the clause. The entries WL-CONVENTIONS and WL-INTEGRITY are not standards: they are the model-consistency checks — a cable missing an end, two identical designations, a conductor size written in mm instead of mm². We run them because no standard covers them, and because an inconsistent design cannot even be checked.

Why the electrical standard changes and the others do not. The cabling and documentation standards Wiring Lab cites — TIA-606, TIA-607, TIA-569, EN 50174-2, the AVIXA ones — are international or regional, and the check is identical everywhere. Electrical installation standards, on the other hand, are national: there the reference changes, and with two profiles (NEC and CEI 64-8 / IEC 60364) so do the thresholds.

Two checks apply in one country only: the minimum conduit diameter (Italy) and the separation between loudspeaker lines and other signals in the same conduit (United States, required by AVIXA). They appear in the list only when you choose that country.

Wiring Lab helps you check a design against the requirements of the standards it cites, and reports the reference behind every check. It is not a certification body and it does not replace verification by a qualified professional.

List of checks as of 11 October 2026. The trademarks and names of the standards belong to their respective owners.